E3LUPS500KHS
Easy UPS 3L 500kVA 400V 3:3 UPS, การเริ่มต้น 5x8
Easy-to-configure, easy-to-use and easy-to-service 500 kVA 3 phase UPS with an exceptional combination of competitive specifications, compact footprint, and highly available parallel and redundant designs. The EcoStruxure Ready Schneider Electric Easy UPS 3L is the easy choice for business continuity on your shop floor, in your electrical room, or in your data center. Includes 5x8 start-up service.
- Easy deployment, with the UPS that is easy to select, configure, start up, use, and service
- Competitive specifications, including robust electrical specifications and ruggedizing features
- Available and resilient, featuring fault-tolerant design and flexible redundancy schemes
- Fast deployment time and low start-up costs, thanks to Smart Test mode
Environmental Data
- การปล่อยก๊าซคาร์บอน
- 651 ton CO2 eq.
Use Better
- Packaging made with recycled cardboard
- No
Use Again
- Recyclability potential, in %
- 1
- Take-back
- No
ข้อมูลจำเพาะ
Main
- Main input voltage
- 400 V AC 3 phases
- Other input voltage
- 380 V415 V
- Maximum input current
- 899 A
- Max short time withstand current
- 35 kA
- Input harmonic distortion
- Less than 3 % for full load
- Load power factor
- 0.5 leading to 0.5 lagging without derating
- Cos phi
- 0.99
- Efficiency at full load
- 323...477 V
- Input frequency
- 40...70 Hz
- Output voltage
- 400 V AC 3 phases
- Other output voltage
- 380 V415 V
- Rated power in W
- 500 kW
- Rated power in VA
- 500 kVA
- Maximum configurable power in VA
- 500 kVA
- Maximum configurable power in W
- 500 kW
- Output harmonic distortion
- < 2% linear load and < 4% non-linear load
- Output overload operation
- 10 minutes at 125% and 60 seconds at 150%
- UPS topology
- Double conversion online
- Output frequency
- 50 Hz sync to mains60 Hz sync to mains
Batteries & Runtime
- Battery type
- External battery system
- Battery voltage
- +/- 216...+/- 300 V
- Discharge battery voltage
- +/- 172.8...+/- 240 V